type se style (R)

Application: 

Style R (SER) Service Entrance Cable is employed for transporting power from the service drop to the meter base and from the meter base to the distribution panel board. It is suitable for both above-ground service entrance and interior wiring applications, with a maximum temperature limit of 90°C. The cable is rated for 600 volts.

product features: 

Standards:

UL Standard 44 compliance is met for XHHW-2 conductors, along with adherence to (UL) Standard 854, Federal Specification JC-30B, and NEC requirements.
ELITE WIRE SER - 2 Conductor with Ground
Size
AWG & 
Const.
Stranding
Phase
Conductors
Equip. Ground
Cond.
Nominal Diameter
(in)
Weight per 1000ft.
(lbs)
Amapacity (AMPS) *
90˚ C
Dwelling
6-6-6
7
-
.650
150
60
-
4-4-6
7
-
.681
196
75
-
4-4-4
7
-
.682
196
75
-
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
Notes: The information is estimated and may be influenced by standard manufacturing tolerances.
To ascertain the appropriate ampacity based on conductor size, refer to the latest edition of the National Electric Code.
ELITE WIRE SER - 3 Conductor with Ground
Size
AWG & 
Construction
Stranding
Phase
Conductors
Equip. Ground
Conductor
Nominal Diameter
(in)
Weight per 1000ft.
(lbs)
Amapacity (AMPS) *
90˚ C
Dwelling
8-8-8-8
Solid
Solid
.588
128
45
-
6-6-6-6
7
7
.684
180
60
-
4-4-4-6
7
7
.754
240
75
-
2-2-2-4
7
7
.893
344
100
100
1-1-1-3
19
7
1.003
432
115
110
1/0-1/0-1/0-2
19
7
1.097
521
135
125
2/0-2/0-2/0-1
19
19
1.197
633
150
150
3/0-3/0-3/0-1/0
19
19
1.314
771
175
175
4/0-4/0-4/0-2/0
19
19
1.443
942
205
200
250-250-250-3/0
37
19
1.601
1106
230
225
300-300-300-4/0
37
19
1.719
1360
255
230
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
The information is estimated and may be influenced by standard manufacturing tolerances.
To ascertain the appropriate ampacity based on conductor size, refer to the latest edition of the National Electric Code.
ELITE WIRE SER - 4 Conductor with Ground
Size
AWG & 
Construction
Stranding
Phase
Conductors
Equip. Ground
Conductor
Nominal Diameter
(in)
Weight per 1000ft.
(lbs)
Amapacity (AMPS) *
90˚ C
Dwelling
2-2-2-2-4
7
7
1.004
450
100
100
2/0-2/0-2/0-2/0-1
19
19
1.346
824
150
150
4/0-4/0-4/0-4/0-2/0
19
19
1.621
1226
205
200
250-250-250-250-3/0
37
19
1.950
1454
230
225
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
The information is estimated and may be influenced by standard manufacturing tolerances.
To ascertain the appropriate ampacity based on conductor size, refer to the latest edition of the National Electric Code.