To provide electricity from the utility's lines to the consumer's weatherhead. Suitable for service at 600 volts or less (phase to phase) with a maximum conductor temperature of 75°C for polyethylene insulation or 90°C for crosslinked polyethylene (XLP) insulated conductors.
product features:
The conductors consist of compressed 1350-H19 aluminum, stranded in a concentric manner. The insulation is either polyethylene or crosslinked polyethylene (XLP). The neutral messengers are concentrically stranded, and they can be made of 6201, AAC, or ACSR.
Standards:
The service drop cable complies with or surpasses the specified ASTM standards:
Aluminum Wire, 1350-H19 for Electrical Applications, designated as B-230.
Aluminum Conductors, Stranded in a Concentric Lay, designated as B-231.
Aluminum Conductors, Concentric-Lay-Stranded, with Coated Steel Reinforcement (ACSR), designated as B-232.
Concentric-Lay-Stranded, Aluminum Alloy Conductors of 6201-T81, designated as B-399.
Compressed Round Stranded Aluminum Conductors utilizing a Single Input Wire, designated as B-901.
ELITE WIRE Triplex Service Drop - AAAC - Alloy Neutral Messenger
Code Word
Insulation Thickness
Size
(AWG)
Strand
Insulation Thickness
(mls)
Bare Neutral
Size
(AWG)
Strand
Breaking Strength
(lbs)
Weight Per 1000 ft.
(lbs)
XLP
Poly
Rating
(AMPS)
XLP
Poly
Minex
6
Solid
45
6
7
1,110
106.6
102.9
85
70
Hippa
6
7/w
45
6
7
1,110
107.0
105.7
85
70
Prawn
4
Solid
45
4
7
1,760
158.4
154.1
110
90
Barnacles
4
7/w
45
4
7
1,760
160.0
157.0
110
90
Shrimp
2
7/w
45
2
7
2,800
243.0
238.0
150
115
Gammarus
1/0
7/w
60
1/0
7
4,460
390.0
384.0
200
155
Leda
1/0
19/w
60
1/0
7
4,460
384.0
378.0
200
155
Dungenese
2/0
7/w
60
2/0
7
5,390
481.0
474.0
230
180
Cyclops
2/0
19/w
60
2/0
7
5,390
473.0
467.0
230
180
Flustra
3/0
19/w
60
3/0
7
6,790
596.0
589.1
260
205
Lepas
4/0
19/w
60
4/0
7
8,560
725.0
716.0
300
235
Swipe left on table to view contents
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
ELITE WIRE Triplex Service Drop - Aluminum Conductor - AAAC - Alloy Reduced Neutral Messenger
Code Word
Insulation Thickness
Size
(AWG)
Strand
Insulation Thickness
(mls)
Bare Neutral
Size
(AWG)
Strand
Breaking Strength
(lbs)
Weight Per 1000 ft.
(lbs)
XLP
Poly
Rating
(AMPS)
XLP
Poly
Artemia
4
Solid
45
6
7
1,110
134.0
132.0
110
90
Crab
4
7/w
45
6
7
1,110
144.0
141.2
110
90
Solaster
2
7/w
45
4
7
1,760
216.0
212.6
150
115
Sandcrab
1/0
7/w
60
2
7
2,800
348.0
341.0
200
155
Echinus
1/0
19/w
60
2
7
2,800
342.0
336.0
200
155
Crayfish
2/0
7/w
60
1
7
3,530
452.6
422.5
230
180
Sipho
2/0
19/w
60
1
7
3,530
441.0
422.5
230
180
Fulgar
3/0
19/w
60
1/0
7
4,460
525.0
518.0
260
205
Arca
4/0
19/w
60
2/0
7
5,360
640.0
632.0
300
235
Swipe left on table to view contents
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
ELITE WIRE Triplex Service Drop - Aluminum Conductor - AAC - Neutral Messenger
Code Word
Insulation Thickness
Size
(AWG)
Strand
Insulation Thickness
(mls)
Bare Neutral
Size
(AWG)
Strand
Breaking Strength
(lbs)
Weight Per 1000 ft.
(lbs)
XLP
Poly
Rating
(AMPS)
XLP
Poly
Haiotis
6
Solid
45
6
7
563
102.5
98.8
85
70
Patella
6
7/w
45
6
7
563
104.0
101.6
85
70
Fusus
4
Solid
45
4
7
881
151.9
147.6
110
90
Oyster
4
7/w
45
4
7
881
154.0
151.7
110
90
Clam
2
7/w
45
2
7
1,350
232.0
228.0
150
115
Murex
1/0
7/w
1/0
1/0
7
1,990
374.0
367.0
200
155
Purpura
1/0
19/w
1/0
1/0
7
1,990
368.0
362.0
200
155
Nassa
2/0
7/w
2/0
2/0
7
2,510
461.0
453.0
230
180
Melita
3/0
19/w
3/0
3/0
19
3,310
585.2
562.9
260
205
Portunus
4/0
19/w
4/0
4/0
19
4,020
693.0
684.0
300
235
Nannynose
336.4
19/w
336.4
336.4
19
6,146
1,111.0
1,096
380
290
Swipe left on table to view contents
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
ELITE WIRE Triplex Service Drop - Aluminum Conductor - Full Size ACSR Messenger
Code Word
Insulation Thickness
Size
(AWG)
Strand
Insulation Thickness
(mls)
Bare Neutral
Size
(AWG)
Strand
Breaking Strength
(lbs)
Weight Per 1000 ft.
(lbs)
XLP
Poly
Rating
(AMPS)
XLP
Poly
Paludina
6
Solid
45
6
6/1
1,190
114
113
85
70
Voluta
6
7/w
45
6
6/1
1,190
115
112
85
70
Whelk
4
Solid
45
4
6/1
1,860
163
161
110
90
Periwinkle
4
7/w
45
4
6/1
1,860
172
169
110
90
Conch
2
7/w
45
2
6/1
2,850
262
257
150
115
Neritina
1/0
7/w
60
1/0
6/1
4,380
420
414
200
115
Cenia
1/0
19/w
60
1/0
6/1
4,380
414
408
200
115
Runcina
2/0
7/w
60
2/0
6/1
5,310
519
512
230
180
Triton
2/0
19/w
60
2/0
6/1
5,310
511
505
230
180
Cherrystone
3/0
7/w
60
3/0
6/1
6,620
656
643
260
205
Mursia
3/0
19/w
60
3/0
6/1
6,620
633
626
260
205
Razor
4/0
7/w
60
4/0
6/1
8,835
814
799
300
235
Zuzara
4/0
19/w
60
4/0
6/1
8,350
785
777
300
235
Limpet
336.4
19/w
80
336.4
18/1
8,680
1,160
1,147
300
290
Swipe left on table to view contents
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
ELITE WIRE Triplex Service Drop - Aluminum Conductor - ACSR Reduced Size Messenger
Code Word
Insulation Thickness
Size
(AWG)
Strand
Insulation Thickness
(mls)
Bare Neutral
Size
(AWG)
Strand
Breaking Strength
(lbs)
Weight Per 1000 ft.
(lbs)
XLP
Poly
Rating
(AMPS)
XLP
Poly
Scallop
4
Solid
45
6
6/1
1,190
142
139
110
90
Strombus
4
7/w
45
6
6/1
1,190
151
148
110
90
Cockle
2
7/w
45
4
6/1
1,860
228
224
150
115
Janthina
1/0
7/w
60
2
6/1
2,850
367
360
200
155
Ranella
1/0
19/w
60
2
6/1
2,850
361
356
200
155
Cavolinia
2/0
7/w
60
1
6/1
3,550
452
444
230
180
Clio
2/0
19/w
60
1
6/1
3,550
444
437
230
180
Sanddollar
3/0
7/w
60
1/0
6/1
4,380
570
557
260
205
Aega
3/0
19/w
60
1/0
6/1
4,380
565
552
260
205
Cutlefish
4/0
7/w
60
2/0
6/1
5,310
706
691
300
235
Cerapus
4/0
19/w
60
2/0
6/1
5,310
678
670
300
235
Cowry
336.4
19/w
80
4/0
6/1
8,350
1,135
1,093
380
290
Swipe left on table to view contents
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
The specified sizes correspond to the ACSR 6/1 diameter equivalent resistivity as per ASTM-B-399 for 6201.
Conductor temperature is 90°C for XLP and 75°C for Poly, with ambient temperatures at 40°C, emissivity of 0.9, and a sun-exposed wind speed of 2ft/sec.
For determining the current ampacity based on conductor size, refer to the most recent edition of The National Electric Code.
The information is an approximation and is susceptible to standard manufacturing tolerances.