Application: 

Service Entrance Cable, identified as Style U (SEU), is designed for use as the main cable to deliver overhead electrical service from the service head to the house meter. It is suitable for both wet and dry conditions and can also be used for interior wiring applications. The cable is rated for 600 volts.

product features: 

Standards:

Conductors of type XHHW-2 conform to UL Standard 44, UL Standard 854, Federal Specification JC-30B, and are approved for use in compliance with the requirements of the 2011 Edition of the NEC NFPA 70.
ELITE WIRE SEU
Size
AWG & Construction
Stranding
Phase
Conductors
Bare Ground
Outside Diameter
(in)
Weight per 1000ft.
(lbs)
Amapacity (AMPS) *
90˚ C
Dwelling
6-6-6
7
11
.458 x .720
143
60
-
4-4-4
7
16
.505 x .811
198
75
-
4-4-6
7
11
.502 x .808
184
75
-
2-2-2
7
15
.559 x .919
282
100
100
2-2-4
7
16
.559 x .919
259
100
100
1/0-1/0-1/0
19
18
.661 x 1.095
438
135
125
1/0-1/0-2
19
14
.647 x 1.095
387
135
125
2/0-2/0-2/0
19
18
.719 x 1.208
516
150
150
2/0-2/0-1
19
14
.702 x 1.190
467
150
150
4/0-4/0-4/0
19
30
.857 x 1.445
770
205
200
4/0-4/0-2/0
19
18
.818 x 1.406
692
205
200