URD Cable

Quadruplex

Application: 

Buried directly or placed in conduits for 600-volt secondary distribution.

product features: 

Concentrically stranded or compressed 1350-H19 aluminum conductor with crosslinked polyethylene insulation. Surface-printed insulated conductors, with neutral options of triple yellow stripes or solid yellow; black neutrals can be specified if desired.

Standards:

UL Standard 854 for Type USE-2, ASTM B-230, B-231, and ICEA S-105-692, as well as Federal Specification JC-30B in accordance with NEC.
ELITE WIRE Quadruplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor
Code
Word
Phase Conductors
Size
(AWG)
Strand
Insulation Thickness
(mls)
Neutral Conductor
Size
(AWG)
Strand
Insulation Thickness
(mls)
Single Phase
Conductor
(in)
Outside
Diameter
(in)
Weight Per
1000ft
(in)
Amapcity
(AMPS)
Direct
Burial
In
Duct
Tulsa
4
7/w
60
4
7/w
60
.345
.833
258
119
85
Dyke
2
7/w
60
4
7/w
60
.403
.938
346
153
115
Wittenberg
2
7/w
60
2
7/w
60
.403
.973
375
153
115
Notre Dame
1/0
19/w
80
2
7/w
60
.522
1.188
541
198
150
Purdue
1/0
19/w
80
1/0
19/w
80
.522
1.260
596
198
150
Syracuse
2/0
19/w
80
1
19/w
80
.566
1.316
664
225
170
Wake Forest
4/0
19/w
80
2/0
19/w
80
.672
1.560
979
290
225
Rust
250
37/w
95
3/0
19/w
80
.748
1.725
1,176
319
240
Slippery Rock
350
37/w
95
4/0
19/w
80
.851
1.945
1,544
385
305
Wofford
500
37/w
95
350
37/w
95
.851
2.348
2,174
467
420
Westminster
750
61/w
110
350
37/w
95
.979
2.722
2,816
615
492
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
  • Ampacity: 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor for a three-conductor triplex with the neutral carrying only an unbalanced load.
  • The cable has XLP insulation with an extruded stripe in a solid yellow color.
  • To ascertain the accurate ampacity based on the conductor size, please refer to the latest edition of the National Electric Code.
  • The provided data is an approximation and is susceptible to standard manufacturing tolerances.