URD Cable

Triplex Tri-Rated

Application: 

Triplex cables of types RHH, RHW-2, or USE-2 are mainly employed for secondary distribution and underground service at 600 volts or less, suitable for both direct burial and installation in ducts. Additionally, they may be utilized in conduits as specified by the NEC.

product features: 

Standards:

UL Standard 44 for Type RHH or RHW-2, and UL Standard 854 for Type USE-2.

ICEA S-105-692 for conductors insulated with cross-linked polyethylene, ASTM B-800 for 8000 Series Aluminum Alloy Wire designed for Electrical Purposes – Annealed and Intermediate Tempers, and ASTM B-801 for concentric lay stranded conductors of 8000 Series Alloy intended for subsequent covering or insulation.
ELITE WIRE Triplex Tri-Rated 600V With White Extruded Strip
Code
Word
Phase Conductors
Size
(AWG)
No. of
Wires
Insulation Thickness
Neutral Conductor
Size
(AWG)
Strand
Insulation
Thickness
Outside
Diameter
(in)
Weight Per
1000ft
(in)
AL
Total
Amapcity
(AMPS)
Direct
Burial
In
Duct
Vassar
4
7
.060
4
7
.060
.745
118
191
125
90
Stephens
2
7
.060
4
7
.060
.875
164
249
165
120
Ramapo
2
7
.060
2
7
.060
.875
184
275
165
120
Brenau
1/0
19
.080
2
7
.060
1.110
261
387
215
160
Bergen
1/0
19
.080
1/0
19
.080
1.110
298
441
215
160
Converse
2/0
19
.080
1
19
.080
1.205
329
478
245
180
Hunter
2/0
19
.080
2/0
19
.080
1.205
375
535
245
180
Sweetbriar
4/0
19
.080
2/0
19
.080
1.421
523
709
315
240
Monmouth
4/0
19
.080
4/0
19
.080
1.421
597
796
315
240
Pratt
250
37
.095
3/0
19
.080
1.590
628
853
345
265
Wesleyan
350
37
.095
4/0
19
.080
1.780
843
1,118
415
320
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
The provided information is an approximation and is within standard manufacturing tolerances.