URD Cable

Triplex

Application: 

Buried directly or placed in conduits for 600-volt secondary distribution.

product features: 

Concentrically stranded or compressed 1350-H19 aluminum conductor with crosslinked polyethylene insulation. Surface-printed insulated conductors, with neutral options of triple yellow stripes or solid yellow; black neutrals can be specified if desired.

Standards:

UL Standard 854 for Type USE-2, ASTM B-230, B-231, and ICEA S-105-692, as well as Federal Specification JC-30B in accordance with NEC.
ELITE WIRE Triplex Conductor 600V Secondary Type URD Cable - Aluminum Conductor
Code
Word
Phase Conductors
Size
(AWG)
Strand
Insulation Thickness
(mls)
Neutral Conductor
Size
(AWG)
Strand
Insulation
Thickness
(mls)
Single Phase
Conductor
(in)
Outside
Diameter
(in)
Weight Per
1000ft
(in)
Amapcity
(AMPS)
Direct
Burial
In
Duct
Erksine
6
7/w
60
6
7/w
60
.299
.646
143
95
70
Vassar
4
7/w
60
4
7/w
60
.345
.754
203
125
90
Stephens
2
7/w
60
4
7/w
60
.403
.842
264
165
120
Ramapo
2
7/w
60
2
7/w
60
.403
.874
294
165
120
Brenau
1/0
19/w
80
2
7/w
60
.522
1.064
408
215
160
Bergen
1/0
19/w
80
1/0
19/w
80
.522
1.133
465
215
160
Converse
2/0
19/w
80
1
19/w
80
.566
1.174
502
245
180
Hunter
2/0
19/w
80
2/0
19/w
80
.566
1.228
560
245
180
Hollins
3/0
19/w
80
1/0
19/w
80
.616
1.276
606
280
205
Sweetbriar
4/0
19/w
80
2/0
19/w
80
.672
1.389
739
315
240
Monmouth
4/0
19/w
80
4/0
19/w
80
.672
1.457
828
315
240
Pratt
250
37/w
95
3/0
19/w
80
.748
1.538
893
345
265
Wesleyan
350
37/w
95
4/0
19/w
80
.851
1.736
1166
415
320
Rider
500
37/w
95
350
37/w
95
.979
2.035
1663
495
395
Fairfield
750
61/w
110
500
37/w
95
1.118
2.860
2304
615
525
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
  • Ampacity: 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor for a three-conductor triplex with the neutral carrying only an unbalanced load.
  • The cable has XLP insulation with an extruded stripe in a solid yellow color.
  • To ascertain the accurate ampacity based on the conductor size, please refer to the latest edition of the National Electric Code.
  • The provided data is an approximation and is susceptible to standard manufacturing tolerances.