For above-ground electrical service utilization, spanning from the service disconnecting means to remote distribution equipment, and under specific conditions permitted by the National Electrical Code (NEC), Type SE Style R may be employed for interior wiring as a branch circuit for ranges, ovens, cooking units, or clothes dryers. This cable adheres to the requirements of Underwriters Laboratories Standard 854, and its installation is approved in line with Articles 215, 225, 230, and 338 of the NEC, featuring a 600-volt rating.
Construction:
Conductors: Conductors are concentrically stranded, with a 7-strand configuration following Class B specifications as per ASTM-B8. Additionally, there is a combination unilay stranded configuration with 19 strands per ASTM-B787.
Insulation: Boasting high dielectric strength, this cable features a heat and moisture-resistant, black or colored Polyvinyl Chloride (PVC) insulation rated at 90°C for wet or dry conditions. It complies with UL-83 standards for THHN or THWN-2 wire.
Conductor Jacket: A transparent Nylon sheath that adheres to the specifications outlined in UL-83 for THHN or THWN-2.
Ground/Neutral Conductor: Uncoated, soft-drawn grounding conductor conforming to ASTM-B3, ASTM-B8, or ASTM-B787.
Overall Jacket: A PVC jacket resistant to sunlight and fungus, colored gray.
Assembly: The conductors are intertwined, and the bare copper grounding conductor is placed in a single gap. A tape reinforced with glass is wrapped around the cabled core.
Standards:
Standards set by Underwriters Laboratories include UL-83, UL-854, and UL-2556, along with Federal Specifications AA59544. Compliant with NEMA RV 4-2012 and relevant sections of NFPA 70 (NEC®) such as Article 215, 225, 230, and 338. In accordance with ARRA 2009 Section 1605 for "Buy American" compliance, and specified in MasterSpec Division 26 Sections 260519 and 260523. UL Listing #E-174428 is also maintained.
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
Conductor ampacity is determined according to NFPA 70 (NEC) Table 310.15(B)(16). Refer to 110.14(C), 240.4(D), 310.15(B), and 338.10(B)(4) for additional limitations where applicable. Also, consult NEC 310.15(B)(7) as appropriate. The provided data is an approximation and is subject to normal manufacturing tolerances.