Copper THHN/THWN-2

Description: 

Type THHN or THWN-2 conductors are predominantly utilized in conduit as branch circuits within commercial or industrial applications, adhering to the specifications outlined by the National Electric Code. Type AWM or MTW conductors are primarily employed for appliance or machine tool wiring, as specified by the National Electric Code. These THHN or THWN-2 conductors are available in stranded forms for sizes 14 AWG to 750 kcmil, and in solid form for sizes 14-10 AWG. Stranded sizes from 14 AWG to 750 kcmil are also rated as AWM or MTW. The conductors, whether soft-annealed, stranded, or solid copper, are insulated with a resilient, heat, and moisture-resistant polyvinyl chloride (PVC). Additionally, a nylon (polyamide) jacket is applied. Sizes 14-750 MCM are equipped with a friction-reducing nylon jacket to facilitate the installation process.

Standards & Specifications:

The cable is rated for 600V and complies with UL standards 83, 1063, and 758. It is designated as sunlight resistant for sizes 1/0 and larger and holds a VW-1 rating. Additionally, it is suitable for cable tray use for sizes 1/0 and larger, in accordance with NEMA Publication No. WC70. The cable exhibits resistance to gasoline and oil, meeting the Gasoline & Oil Resistant II standard. It carries the c(UL) certification for all sizes and is compliant with ARRA 2009 Section 1605
ELITE WIRE THHN/THWN
Conductor
Size
(AWG)
Stranding
Insulation Thickness
(in)
Jacket
Thickness
(mils)
Nominal O.D.
(mils)
Weight Per 1000 ft
(lbs)
Ampacity
(AMPS) *90° C
8
19
.030
5
218
64
55
6
19
.030
5
256
96
75
4
19
.040
6
325
155
95
2
19
.040
6
388
235
130
1
19
.050
7
437
300
150
1/0
19
.050
7
477
370
170
2/0
19
.050
7
521
465
195
3/0
19
.050
7
571
570
225
4/0
19
.050
7
627
720
260
250
37
.060
8
711
850
290
300
37
.060
8
766
1,011
320
350
37
.060
8
817
1,172
350
400
37
.060
8
864
1,333
380
500
37
.060
8
949
1,653
430
600
61
.070
9
1,051
1,985
475
750
61
.070
9
1,126
2,462
535
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
*The provided allowable ampacity is in accordance with the National Electrical Code. The presented data is an approximation and is subject to standard manufacturing tolerances.