Aluminum 600v Photovoltaic Cable

Application: 

Aluminum PV Photovoltaic Cable is designed for interconnection wiring within grounded and ungrounded photovoltaic power systems. The cable is suitable for applications up to 600 volts and can endure temperatures ranging from -40°C to +90°C, whether wet or dry.

construction: 

Standards:

ASTM B800, B801, B836, B901 standards apply. The PV Wire is UL listed according to UL 4703. Type RHH/RHW-2 or USE-2 complies with UL 44 and UL 854. It is UL listed for VW-1 and Sunlight Resistant. Additionally, it is UL listed for Direct Burial in sizes 6AWG and larger.
ELITE WIRE 600V aluminum PV
Conductor
Size
(AWG/kcmil)
Stranding
Insulation
Thickness
(in)
Overall
Diameter
(in)
Weight Per 1000 ft.
(lbs)
DC Resistance
at 20°C
(Ω/kft)
Ampacity 90°C
(AMPS)
8**
7
.075
.29
42
1.504
45
6
7
.075
.32
51
.6609
55
4
7
.075
.36
71
.4155
75
2
7
.075
.42
101
.2613
100
1
19
.095
.49
136
.2072
115
1/0
19
.095
.53
163
.1642
135
2/0
19
.095
.57
195
.1303
150
3/0
19
.095
.61
236
.1033
175
4/0
19
.095
.67
286
.0820
205
250
37
.110
.74
343
.0694
230
300
37
.110
.79
400
.0578
260
350
37
.110
.84
455
.0495
280
400
37
.110
.88
501
.0434
305
500
37
.110
.96
608
.0347
350
600
61
.125
1.06
737
.0289
385
750
61
.125
1.16
896
.0231
435
1,000
61
.125
1.31
1,161
.0173
500
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
All provided values are approximate and subject to correction. The ampacities are derived from Table 310.15(B)(16) of the NEC 2017 Edition, considering no more than three current-carrying conductors, with conductor temperatures at 90°C and an ambient temperature of 30°C.
**Not rated for direct burial.