Copper Photovoltaic Cable

Application: 

Copper Photovoltaic Cable is predominantly utilized for interconnection wiring in grounded and ungrounded photovoltaic power systems. The cable is suitable for applications with voltages up to 600V or 2KV as per the rated voltage, and it can withstand temperatures ranging from -40°C to +90°C in both wet and dry conditions.

construction: 

Standards:

ASTM B3, B8, or B787, UL-listed PV wire per UL4703, and RHH RHW-2 USE-2 per UL 44 and UL 854 are specifications for the Copper Photovoltaic Cable. This cable is identified as Sunlight Resistant and Direct Burial, holding UL listing for the FV-1 flame test.
ELITE WIRE 2KV Copper PV
Conductor
Size
(AWG/kcmil)
Stranding
Insulation
Thickness
(mils)
Overall
Diameter
(mils)
Weight Per 1000 ft.
(lbs)
DC Resistance
at 20°C
(Ω/kft)
Ampacity 90°C
(AMPS)
10
7 or 19
75
266
57
1.0200
40
8
7 or 19
85
316
86
.6400
55
6
7
85
354
121
.4030
75
4
7
85
402
176
.2530
95
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
All values are approximate and subject to correction. Refer to NEC 240.4(D) for limitations on conductor overcurrent protection. Ampacities are derived from NEC 2017 Edition Table 310.15(B)(16) for a maximum of three current-carrying conductors at conductor temperatures of 90°C and an ambient temperature of 30°C.