Type G-GC 90°C 2000V

Application: 

Type G-GC is designed for robust applications, serving as a power supply cable for mobile and portable mining equipment, including loaders, conveyors, pumps, drills, and cutters. It is suitable for scenarios demanding flexibility and features an internal ground check conductor for enhanced safety. Type G-GC is intended for use in applications up to 2000 volts, with a temperature range spanning from -40°C to +90°C.

construction: 

Standards:

UL 44 and 1650, C(UL) FT1 & FT5, CSA C22.2 96-13, ICEA S-75-381/NEMA WC 58, ICEA S-95-658/NEMA WC 70, ASTM B33, B172. The cable is oil-resistant, and sunlight-resistant in both wet and dry conditions, and it is rated and flexible at temperatures ranging from -40ºC to +90°C.
ELITE WIRE Type G-GC 90°C 2000V
Conductor
(AWG/#)
Stranding
Ground Conductor
Size
(AWG)
Ground
Check
Size
(AWG)
Insulation
Thickness
(in)
Overall
Diameter
(lbs)
Weight Per 1000 ft.
(lbs)
Ampacity 30°C
in Air
(AMPS)
8-3
133
2 # 10
10
.060
.990
666
65
6-3
133
2 # 10
10
.060
1.050
787
87
4-3
259
2 # 8
10
.060
1.140
1,048
114
2-3
259
2 # 7
8
.060
1.300
1,448
152
1-3
259
2 # 6
8
.080
1.460
1,807
177
1/0-3
266
2 # 5
8
.080
1.600
2,206
205
2/0-3
342
2 # 4
8
.080
1.750
2,736
237
3/0-3
418
2 # 3
8
.080
1.860
3,178
274
4/0-3
532
2 # 2
8
.080
1.960
3,718
316
250-3
627
2 # 1
6
.095
2.390
4,917
352
350-3
888
2 # 1/0
6
.095
2.680
6,449
433
500-3
1,221
2 # 3/0
6
.095
3.030
8,642
536
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
Nominal values are provided and are subject to correction. Ampacities are based on a 90ºC conductor and a 30ºC ambient temperature, as per table 400.5(A)(2) of the National Electrical Code.