Type MP-GC 90°C 15KV

Application: 

Type MP-GC is designed for high voltage connections in mines, mine tunnels, shafts, and mine load centers, where an internal ground check conductor is necessary for enhanced safety. This cable is suitable for installation in ducts, troughs, trays, or for direct burial in non-flexing applications. It is intended for use in applications up to 15,000 volts and can withstand temperatures ranging from -20°C to +90°C.

construction: 

Standards:

Portable and power feeder cables designed for use in mines and similar applications, compliant with ICEA S-75-381/NEMA WC58 standards.
ELITE WIRE Type MP-GC 90°C 15KV
Conductor
(AWG/kcmil)
Stranding
Ground
Size
(AWG)
Ground
Check
Size
(AWG)
Insulation
Thickness
(in)
Jacket
Thickness
(in)
Outside
Diameter
(lbs)
Weight Per 1000 ft.
(lbs)
2
7
6
8
.175
.140
1.880
2,190
1/0
19
4
8
.175
.140
2.050
2,890
2/0
19
3
8
.175
.140
2.150
3,350
4/0
19
1
8
.175
.140
2.400
4,610
250
37
1/0
6
.175
.140
2.500
4,990
350
37
2/0
6
.175
.140
2.750
6,380
500
37
4/0
6
.175
.170
3.100
8,770
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
All values are approximate and subject to adjustment.