Tray Cable - With Ground - 6 AWG - 4/0 AWG - 600V

THHN/THWN-2 Conductors

Application: 

Mainly employed for connecting power devices in commercial and industrial environments. Appropriate for installation in electrical channels, ducts, wireways, cable trays, and raceways. Endorsed for direct burial in wet or dry locations and outdoor use in cable trays where a sunlight-resistant rating is necessary. The cable is formulated and certified for applications requiring a type TC-ER rating. For cables that require Class 1 Division II Hazardous Location ratings, please consult with your local Elite Wire representative.

product features: 

Standards:

Compliant with standards including UL-83, UL-1277, UL-1581, UL-1685, UL-2556; features Compact Stranded Aluminum Alloy 8000 Series as per ASTM B800, ASTM B801, ASTM B836; follows NFPA 70 (NEC®) Article 336; passes UL-1685 FT4/IEEE 1202 (70,000 Btu/hr) Flame Test; meets NEMA WC70/ICEA S-95-658; complies with ICEA T-29-520 (210,000 Btu/hr) Flame Test; is RoHS Compliant; conforms to MasterSpec Division 26 Sections 260519, 260523; and holds UL Listing #E-179429.
ELITE WIRE TRAY CABLE - With Ground - 6 AWG - 4/0 AWG - 600V
Size
# Of
Conductors
Stranding
Ground Wire
Size
(AWG)
# Strands For Ground
Outer Jacket
Thickness PVC
(in)
3
4
Outside
Diameter
(in)
3
4
Weight Per
1000 Feet
(lb)
3
4
Ampacity
(Amps)1
75°C
90°C
6
3
4
7
6
7
.060
.060
.710
.778
257
316
50
55
4
3
4
7
6
7
.080
.080
.872
.965
361
450
65
75
3
3
4
7
6
7
.060
.060
.920
1.020
430
536
75
85
2
3
4
7
6
7
.080
.080
.977
1.086
496
618
90
100
1
3
4
8
4
7
.060
.060
1.113
1.236
630
787
100
115
1/0
3
4
10
4
7
.080
.080
1.184
1.320
733
908
120
135
2/0
3
4
12
4
7
.060
.060
1.260
1.408
865
1,070
135
150
3/0
3
4
15
4
7
.080
.080
1.350
1.512
1,025
1,275
155
175
4/0
3
4
19
2
7
.060
.060
1.476
1.654
1,236
1,551
180
205
The tables are large, so you will need to use your fingers to swipe left to view all columns of data.
1 Refer to NEC Table 310.15(B)(16) for insulated conductor ampacities, considering not more than three current-carrying conductors in a raceway, cable, or earth (directly buried), with an ambient temperature of 30°C (86°F). For ambient temperature correction factors other than 30°C (86°F), consult NEC Article 310.15(B)(2)(a). Utilize NEC Table 310.15(B)(3)(a) for ampacity adjustment factors, as applicable, when dealing with more than three current-carrying conductors. For conductor temperature limitations for equipment rated 100 amps or less, or for equipment rated for more than 100 amps, refer to NEC Article 110.14(C). The provided data is approximate and subject to manufacturing tolerances.